General
Display: Upper display: 0.60" (15 mm) high. Lower display: 0.46" (12 mm) high. Both are 6 digits (-99999 to 999999), red LEDs.
Resolution: 1° (up to four digits) or 0.1° (up to five digits)
Display Intensity: Eight intensity levels
Display Update Rate: 5/second (200 ms)
Programming Methods: Four through-glass CapTouch buttons, four mechanical buttons behind glass, digital inputs, PC and MeterView Pro software, or Modbus registers.
F4 Digital Input Contacts: 3.3 VDC on contact. Connect normally open contacts across F4 to COM.
F4 Digital Input Logic Levels: Logic High: 3 to 5 VDC; Logic Low: 0 to 1.25 VDC
Noise filter: Programmable from 2 to 199 (0 will disable filter)
Filter Bypass: Programmable from 0.1 to 99.9% of span
Recalibration: Recommended at least every 12 months.
Max/Min Display: Max / min temperature readings are stored until reset by the user or until power to the meter is cycled.
Non-Volatile Memory: All programmed settings are stored in nonvolatile memory for a minimum of ten years if power is lost.
Power Options: 85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max, or optional model with 12-24 VDC ±10%, 15 W max.
Normal Mode Rejection: Greater than 65 dB at 50/60 Hz
Isolation: 4 kV input/output-to-power line. 500 V input-to-output
Environmental:
T6 Class operating temperature range Ta = -55 to 60°C
T5 Class operating temperature range Ta = -55 to 65°C
Storage temperature range: -55 to 85°C (-67 to 185°F)
Relative humidity: 0 to 90% non-condensing
Max Power Dissipation: Maximum power dissipation limited to 15.1 W.
Connections: Removable screw terminal blocks accept 12 to 22 AWG wire, RJ45 for external relays, digital I/O, and serial communication adapters.
Mounting: Four slotted flanges for wall mounting or NPS 1½" to 2½" or DN 40 to 65 mm pipe mounting
Dimensions: 6.42" x 7.97" x 8.47" (W x H x D) (163 mm x 202 mm x 215 mm)
Weight: Aluminum: 14.7 lbs (6.67 kg); Stainless Steel: 23.5 lbs (10.66 kg)
Warranty: 3 years parts & labor
USB Connection: Compatibility: USB 2.0 Standard, Compliant
Connector Type: Micro-B receptacle
Cable: USB A Male to Micro-B Cable
Driver: Windows 98/SE, ME, 2000, Server 2003/2008, XP 32/64-Bit,
Vista 32/64-Bit, Windows 7 32/64-Bit, Windows 10 32/64-Bit
Power: USB Port
Temperature Input
Inputs: Thermocouple J, K, T, E, R, S, B, N, C; RTD 100 Ω platinum (0.00385 & 0.00392 curves), 10 Ω copper, 120 Ω nickel, 1000 Ω platinum
Input Impedance: Greater than 100 k Ω
Offset Adjust: User programmable offset adjust ±50.0 degrees
Temperature Drift: ±2°C maximum from 0 to 65°C ambient temperature; ±4°C maximum from -20 to 0°C ambient temperature
Sensor Break: Display flashes "Open", relays can be programmed to go "On", "Off", or to "Ignore" (detected as an upscale condition).
Averaging: Up to 10 RTDs connected in parallel can be averaged.
Accuracy & Range:
Type | Range (°F) | Range (°C) | Accuracy |
J | -200 to 2000 | -129 to 1093 | ±1°C |
K | -200 to 2400 | -129 to 1316 | ±1°C |
T | -200 to 752 | -129 to 400 | ±1°C |
E | -200 to 1800 | -129 to 982 | ±1°C |
R | -50 to 3000 | -46 to 1649 | ±2°C |
S | -50 to 3000 | -46 to 1649 | ±2°C |
B | 752 to 3300 | 400 to 1816 | ±2°C |
N | -100 to 2300 | -73 to 1260 | ±2°C |
C | 32 to 4100 | 0 to 2260 | ±2°C |
10 Ω | -328 to 500 | -200 to 260 | ±0.1°C |
100 Ω | -328 to 1562 | -200 to 850 | ±0.4°C |
120 Ω | -110 to 500 | -79 to 260 | ±0.1°C |
1000 Ω | -328 to 900 | -200 to 482 | ±0.4°C |
Relays
Rating: 4 SPDT (Form C) internal and/or 4 SPST (Form A) external; rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (≈ 50 watts) @ 125/250 VAC for inductive loads such as contactors, solenoids, etc.
Noise Suppression: Noise suppression is recommended for each relay contact switching inductive loads.
Deadband: 0-100% of span, user programmable
High or Low Alarm: User may program any alarm for high or low trip point. Unused alarm LEDs and relays may be disabled (turned off).
Relay Operation: automatic (non-latching), latching (requires manual acknowledge), sampling (based on time), pump alternation control (2 to 8 relays), Off (disable unused relays and enable interlock feature, manual on/off control mode).
Time Delay: 0 to 999.9 seconds, on & off relay time delays. Programmable and independent for each relay.
Fail-Safe Operation: Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm condition. In case of power failure, relay will go to alarm state.
Auto Initialization: When power is applied to the meter, relays will reflect the state of the input to the meter.
Isolated 4-20 mA Transmitter Output
Output Source: PV (temperature), max, min, set points 1-8, manual control setting, or Modbus input
Scaling Range: 1.000 to 23.000 mA for any display range
Calibration: Factory calibrated 4-20 mA output
Accuracy: ±0.1% of span ± 0.004 mA
Temperature Drift: 0.4 µA/°C max from 0 to 65°C ambient, 0.8 µA/°C max from -40 to 0°C ambient
Note: Analog output drift is separate from input drift.
Isolated Transmitter Power Supply: Terminals I+ & R: 24 VDC ± 10%. Isolated from the input at >500 V. May be used to power the 4-20 mA output or other devices. All models @ 25 mA max.
External Loop Power Supply: 35 VDC maximum
Output Loop Resistance:
Power supply | Minimum | Maximum |
24 VDC | 100 Ω | 7000 Ω |
35 VDC (external) | 100 Ω | 1200 Ω |
Serial Communications
Compatability: EIA-485
Connectors: Removable screw terminal connector
Max Distance: 3,937' (1,200 m) max
Status Indication: Separate LEDs for Power (P), Transmit (TX), and Receive (RX)
Protocol: Modbus® RTU
Meter Address/Slave ID: 1 - 247
Baud Rate: 300 - 19,200 bps
Transmit Time Delay: Programmable between 0 and 199 ms or transmitter always on for RS-422 communication
Data: 8 bit (1 start bit, 1 or 2 stop bits)
Parity: Even, odd, or none with 1 or 2 stop bits
Byte-to-Byte Timeout: 0.01 - 2.54 seconds
Turn Around Delay: Less than 2 ms (fixed)
Digital Inputs and Outputs
Channels: 4 digital inputs & 4 digital outputs per module
System: One expansion module may be added for a total of 8 inputs & 8 outputs
Note: The jumper located between the RJ45 connectors must be removed on the expansion module.
Digital Input Logic: High: 3 to 5 VDC; Low: 0 to 1.25 VDC
Digital Output Logic: High: 3.1 to 3.3 VDC; Low: 0 to 0.4 VD
Source Current: 10 mA maximum output current
Sink Current: 1.5 mA minimum input current
+5 V Terminal: To be used as pull-up for digital inputs only. Connect normally open pushbuttons across +5 V & DI 1-4. Warning: DO NOT use +5 V terminal (pin 1) to power external devices.
Function Assignment: The on-board digital inputs (1-4) are designed to mimic the behavior of the front panel buttons (Menu, F1, F2, & F3). If you wish to change their behavior, re-assign F1-F3 to the desired function, then change the corresponding digital input to match.
Enclosure
Material | -AL Models: ASTM A413 LM6 die-cast aluminum, copper-free, enamel coated -SS Models: ASTM A743 CF8M investment-cast 316 stainless steel |
Gasket | Fluoroelastomer |
Rating | NEMA 4X, IP68 Explosion-proof |
Color | -AL: Blue
-SS: Silver |
Window | Borosilicate glass |
Conduits | Four ¾" NPT threaded conduit openings |
Conduit Stopping Plugs | Sold separately |
Flanges | Two built-in flanges for wall and pipe mounting. |
Tamper-Proof Seal | Cover may be secured with tamper-proof seal. |
Overall Dimensions | 6.42" x 7.97" x 8.47" (W x H x D) (163 mm x 202 mm x 215 mm) |
Weight | Aluminum: 14.7 lbs (6.67 kg) Stainless Steel: 23.5 lbs (10.66 kg) |
ATEX | Flameproof II 2GD Ex db IIC Gb Ex tb IIIC Db IP66/IP68 Tamb: -55°C to +85°C Certificate No.: Sira 19ATEX1252U |
IECEx | Flameproof and dust protection Ex db IIC Gb Ex tb IIIC Db IP66/IP68 Tamb: -55°C to +85°C Certificate No.: IECEx SIR 19.0075U |
CSA | Class I, Division 1, Groups A, B, C, D
Class II, Division 1, Group E, F, G
Class III Ex db IIC Gb Ex tb IIIC Db Class I, Zone 1, AEx db IIC Gb Zone 21, AEx tb IIIC Db IP66/IP68/TYPE 4X Tamb: -55°C to +85°C Certificate No.: 80011200 |
UL | Class I, Division 1, Groups A, B, C, D Class II, Division 1, Groups E, F, G Class III Class I, Zone 1, AEx db IIC Gb Zone 21, AEx tb IIIC Ex db IIC Gb Ex tb IIIC Db IP66/IP68/TYPE 4X Tamb: -55°C to +85°C Certificate Number: E518920 |
Note: The above approvals are for the enclosure only. See below for approvals on the entire instrument. |
General Compliance Information
Electromagnetic Compatibility
Emissions | EN 55022 Class A ITE emissions requirements |
Radiated Emissions | Class A |
AC Mains Conducted Emissions | Class A |
Immunity | EN 61326-1 Measurement, control, and laboratory equipment EN 61000-6-2 EMC heavy industrial generic immunity standard |
RFI - Amplitude Modulated | 80 -1000 MHz 10 V/m 80% AM (1 kHz) 1.4 - 2.0 GHz 3 V/m 80% AM (1 kHz) 2.0 - 2.7 GHz 1 V/m 80% AM (1 kHz) |
Electrical Fast Transients | ±2kV AC mains, ±1kV other |
Electrostatic Discharge | ±4kV contact, ±8kV air |
RFI - Conducted | 10V, 0.15-80 MHz, 1kHz 80% AM |
AC Surge | ±2kV Common, ±1kV Differential |
Surge | 1KV (CM) |
Power-Frequency Magnetic Field | 30 A/m 70%V for 0.5 period |
Voltage Dips | 40%V for 5 & 50 periods 70%V for 25 periods |
Voltage
Interruptions | <5%V for 250 periods |
Note: Testing was conducted on meters with cable shields grounded
at the point of entry representing installations designed to optimize
EMC performance. |
Product Ratings and Approvals
CSA | Class I, Division 1, Groups B, C, D Class II, Division 1, Groups E, F, G Class III, Division 1, T5 Class III, Division 1, T6 (Ta max = 60°C) Ex db IIC T5 Ex db IIC T6 (Ta max = 60°C) Ex tb IIIC T90°C Ta = -55°C to +65°C Enclosure: Type 4X & IP66 / IP68 CSA Certificate: CSA 12 2531731 |
ATEX | II 2 G D Ex db IIC T* Gb Ex tb IIIC T90°C Db IP68 Ta = -55°C to +*°C *T6 = -55°C to +60°C *T5 = -55°C to +65°C Certificate Number: Sira 12ATEX1182X
|
IECEx | Ex db IIC T* Gb Ex tb IIIC T90°C Db IP68 Ta = -55°C to +*°C *T6 = -55°C to +60°C *T5 = -55°C to +65°C Certificate Number: IECEx SIR 12.0073X
|
ATEX/IECEx Specific Conditions of Use:- The equipment label and epoxy coating may
generate an ignition-capable level of electrostatic
charges under certain extreme conditions. The
user should ensure that the equipment is not
installed in a location where it may be subjected
to external conditions (such as high-pressure
steam) which might cause a build-up of
electrostatic charges on non-conducting
surfaces. Additionally, cleaning of the equipment
should be done only with a damp cloth.
- Flameproof joints are not intended to be repaired.
- All entry closure devices shall be suitably certified
as “Ex d”, “Ex t” and “IP66/68” as applicable.
Suitable thread sealing compound (non-setting,
non-insulating, non-corrosive, not solvent based,
suitable for the ambient rating) must be used at
the NPT conduit entries to achieve the IPx8
rating while maintaining the Ex protection
concept.
Year of ConstructionThis information is contained within the serial number
with the first four digits representing the year and
month in the YYMM format.
For European Community:The ProtEX-MAX must
be installed in accordance with the ATEX directive
2014/34/EU, and the product certificate Sira
12ATEX1182X.